-
Welcome to Accuthermo Technology Corp.
-
A Total Thermal Solution Provider
Part Number
The unit will come standard with PT100, -200~600°C, you can change the input Type/Rang using the free software " " with the configuration cable URC-1020, or you can contact us for non-standard Input/Rang setting.
Model No. |
Mount type |
IST-H |
Head mount |
The IST-H is user configurable using our software on your PC/notebook or our dedicated handheld programmer. The easy to use software is available free from your supplier or can be downloaded from our web site and should be used in conjunction with the URC-1020 USB cable which incorporates an interface converter necessary for communications.The IST-H transmitter can be configured without any loop or power connected making it easy to configure in the workshop before installation.
The unit will come standard with PT100, -200~600°C, you can change the input Type/Rang using the free software "" with the configuration cable URC-1020, or you can contact us for non-standard Input/Rang setting.
Specification
Input |
Thermocouple (T/C) : industry standard thermocouple types J, K, T, E, B, R, S, N, C (ITS-90). |
Pt100: Excitation 180uA. 2 or 3 wire connection (ITS-90 α =0.00385). |
Voltage: -60mVdc to 60mVdc or –10Vdc to 10Vdc. |
Current : 0-24mAdc |
Accuracy |
Refer to Table 1 Input Signal |
A/D Resolution
|
16 bits |
Input Sampling Rate
|
<200ms |
Power supply |
DC 10 to 36V |
Max. Load |
(V-10)/0.02 ( Ω ) |
Output Resolution
|
0.6 μ A(15 bits) |
Output Response time
|
<200ms |
Common Mode Rejection Ratio(CMRR) |
>80dB |
Electromagnetic compatibility |
En 50081-2, En 50082-2 |
Galvanic isolation |
3.75 KV. between input and output |
Operating Temperature |
-40 to 85 ° C |
Humidity |
0 to 90% RH |
Table 1 Input Signal
Input signal |
Maximum Range |
Accuracy |
Thermocouple J |
-50 to 1000 ° C (-58 to 1832 ° F ) |
± 1 ° C |
Thermocouple K |
-50 to 1370 ° C (-58 to 2498 ° F ) |
± 1 ° C |
Thermocouple T |
-270 to 400 ° C (-454 to 752 ° F ) |
± 1 ° C |
Thermocouple E |
-50 to 700°C (-58 to 1292°F) |
± 1 ° C |
Thermocouple B |
0 to 1750 ° C (32 to 3182 ° F ) |
± 2 ° C (Note1) |
Thermocouple R |
-50 to 1750 ° C (-58 to 3182 ° F ) |
± 2 ° C |
Thermocouple S |
-50 to 1750 ° C (-58 to 3182 ° F ) |
± 2 ° C |
Thermocouple N |
-50 to 1300 ° C (-58 to 2372 ° F ) |
± 2 ° C |
Thermocouple C |
-50 to 1800 ° C (-58 to 3272 ° F ) |
± 2 ° C |
Pt100 |
-200 to 600 ° C (-328 to 1112 ° F ) |
± 0.2 ° C |
mV |
-60mVto 60mV |
± 0.01m V |
Voltage (Note2) |
-10 to 10Vdc |
± 1m V |
Current (Note2) |
0 to 24mAdc |
± 10μA |
Note 1 : Accuracy is not guaranteed between 0 and 400°C (0 and 752°F) for type B
Note 2 : If you require either mV V or mA please specify with order.
Dimension
Wiring Diagram
Block Diagram
Download
|
|
|
Manual |
ISWinC100625 |
Data sheet |
Accessories
|
|
EzPro Handheld Programmer |
URC-1020 Interface Cable |
|